KOROK is proud to have contributed to one of Auckland’s most distinctive new developments — the Indigo Hotel and Apartments at 51 Albert Street. This iconic project brings together a 4.5-star lifestyle hotel, luxury branded residences, and vibrant food and beverage offerings, all within a uniquely challenging site: a slender 41-storey tower rising from a historic 1912 heritage façade.
Designed by Scott Carver and Dalman Architects and delivered by ICON Construction, the Indigo Hotel and Apartments is a shining example of how careful planning, construction innovation, and respect for heritage can work hand in hand to create a new city landmark.
The development’s highly constrained inner-city site presented several key construction challenges:
A tight building footprint within a heritage-listed façade.
Stakeholder sensitivities, with close proximity to neighbouring residents, businesses, and the historic St Patrick’s Cathedral.
The need for high productivity and precision construction techniques on a vertical build of this scale.
ICON Construction’s advanced project management systems and meticulous construction methodologies ensured these challenges were met head-on, delivering an exceptionally efficient build process.
KOROK’s Solution
To meet the stringent fire and acoustic performance requirements across the tower’s external walls, risers, and duct systems, KOROK supplied our 78mm fire and acoustic rated panel system.
Our panels were selected for their:
Lightweight nature, critical for high-rise construction.
Exceptional fire protection performance for vertical service penetrations and separation zones.
Superior acoustic insulation, ensuring a premium experience for both hotel guests and apartment residents.
Rapid installation advantages, helping ICON maintain construction momentum within a tight delivery program.
As a pre-finished system, KOROK panels also contributed to reducing on-site finishing work, a key benefit on a project with constrained site logistics and limited laydown space.
Project Highlights
The Indigo Hotel and Apartments development stands out not only for its scale but for its storytelling and celebration of Auckland’s evolving identity.
The hotel interiors creatively blend industrial elements with heritage materials such as exposed brick, reclaimed timber, and vintage automotive references.
The modern tower’s guest rooms maintain a refined industrial feel, incorporating subtle local cultural references that connect guests to the heart of the city.
The podium revitalizes Auckland’s historic entertainment district, contributing new life and energy to a growing cultural hub.
At KOROK, we are proud that our systems play a quiet but vital role in supporting developments like Indigo Hotel and Apartments — delivering life-safety, acoustic comfort, and buildability for landmark projects that help shape the future of our cities.
When it comes to passive fire penetrations, KOROK® leads the way with innovative solutions that ensure fire safety without compromising functionality.
At KOROK®, we are committed to providing fire-rated wall systems that prioritize safety, durability, and performance. Our advanced KOROK® panels are specifically designed to allow seamless integration of passive fire penetrations, including service ducting and pipes, while maintaining the structural and fire integrity of the wall.
Passive fire penetrations are openings or pathways in fire-rated walls or floors that allow services such as plumbing, electrical cables, or ductwork to pass through. These penetrations are essential for building functionality but must be carefully designed to prevent the spread of fire and smoke. KOROK® panels are engineered to make the creation and sealing of these penetrations straightforward and effective, ensuring compliance with strict fire safety standards.
Why Choose KOROK® for Passive Fire Penetrations?
Easy Formations for Penetrations: KOROK® panels simplify the creation of openings for ducting and plumbing. The lightweight yet robust design makes it easy to form precise and efficient penetrations without compromising fire safety or wall integrity.
Maintained Wall Integrity: Even with multiple passive fire penetrations, KOROK® panels ensure the overall wall system retains its fire rating. This is crucial for preventing fire and smoke from spreading across compartments in a building.
Versatile Applications: Whether your project involves commercial spaces, residential apartments, or industrial facilities, KOROK® passive fire penetrations provide a reliable and efficient solution tailored to meet your needs.
Compliance with Building Codes: KOROK® panels are rigorously tested and meet or exceed New Zealand’s building code requirements for passive fire protection. This gives architects, engineers, and builders confidence in the safety and performance of their projects.
The list below contains a basic selection of tested passive fire solutions, for quick reference. For additional solutions please contact the relevant passive fire companies:
CFS-C P 50/1.5" Fire Collar + CP606 Acrylic Sealant
-/120/60
Hilti
40mm ND uPVC Pipe. Refer to pages 28-30
40mm
uPVC
CFS-C P 50/1.5" Fire Collar + CP606 Acrylic Sealant + 13mm Plasterboard Patch
-/120/90
Hilti
50mm ND uPVC Pipe. Refer to pages 28-30
50mm
uPVC
CFS-C P 63/2.0" Fire Collar + CP606 Acrylic Sealant
-/120/90
Hilti
50mm ND uPVC Pipe. Refer to pages 28-30
50mm
uPVC
CFS-C P 63/2.0" Fire Collar + CP606 Acrylic Sealant + 13mm Plasterboard Patch
-/120/120
Hilti
65mm ND uPVC Pipe. Refer to pages 28-30
65mm
uPVC
CFS-C P 75/2.5" Fire Collar + CP606 Acrylic Sealant
-/120/90
Hilti
65mm ND uPVC Pipe. Refer to pages 28-30
65mm
uPVC
CFS-C P 75/2.5" Fire Collar + CP606 Acrylic Sealant + 13mm Plasterboard Patch
-/120/120
Hilti
80mm ND uPVC Pipe. Refer to pages 28-30
80mm
uPVC
CFS-C P 90/3" Fire Collar + CP606 Acrylic Sealant
-/120/90
Hilti
80mm ND uPVC Pipe. Refer to pages 28-30
80mm
uPVC
CFS-C P 90/3" Fire Collar + CP606 Acrylic Sealant + 13mm Plasterboard Patch
-/120/120
Hilti
Cable Bundle ≤ 36mm Dia. Any combination of Telecommunication cables, Cat5/6/7/8, Fiber Optic cables,RG6 Quad Shield Coax or TPS 2C+E up to 2.5mm2. Refer to pages 13-14
Max. 36mm
Cable
CP611a / CFS-IS Intumescent Sealant
-/120/60
Hilti
Cable Bundle ≤ 36mm Dia. Any combination of Telecommunication cables, Cat5/6/7/8, Fiber Optic cables,RG6 Quad Shield Coax or TPS 2C+E up to 2.5mm2. Refer to pages 13-14
Max. 36mm
Cable
CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/120/90
Hilti
Cable Tray up to 600mm Wide with 9 x 400mm2 XLPE/PVC or PVC/PVC Sheath/Insulated Single Core Copper or Aluminum Power Cables. Refer to pages 21-27
Cable
2 x Layers CP670 Coated Board + CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/60/60
Hilti
Cable Tray up to 600mm Wide with AS1530.4 Standard D1 XLPE/PVC or PVC/PVC Sheath/Insulated Power Cables Cable Sets. Refer to pages 21-27
Cable
2 x Layers CP670 Coated Board + CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/120/90
Hilti
Cable Tray up to 600mm Wide with AS1530.4 Standard D2 Telecommunication Cable Sets. Refer to pages 21-27
Cable
2 x Layers CP670 Coated Board + CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/90/60
Hilti
Up to 10 of Quad Shield Coax Cables. Refer to pages 13-14
Cable
CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/120/90
Hilti
Up to 16 of Telecommunication cables, Cat5/6/7/8 & Fiber Optic cables. Refer to pages 13-14
Cable
CP611a / CFS-IS Intumescent Sealant
-/120/90
Hilti
Up to 16 of Telecommunication cables, Cat5/6/7/8 & Fiber Optic cables. Refer to pages 13-14
Cable
CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage
-/120/120
Hilti
Up to 8 of TPS 2C+E up to 2.5mm2. Refer to pages 13-14
CP611a / CFS-IS Intumescent Sealant
-/120/60
Hilti
Up to 8 of TPS 2C+E up to 2.5mm2. Refer to pages 13-14
CP611a / CFS-IS Intumescent Sealant + CFS-P BA Putty Bandage