5171KI KOROK® Intertenancy Wall Systems Specification

5171KI KOROK® Intertenancy Wall Systems Specification

var el = document.createElement('script'); el.src = 'https://masterspec.co.nz/assets/javascript/masterspec.js'; el.onload = function() {var mylnk = _lnk("7fbd0cae-3a5c-417f-abb2-fcbebf68739b");mylnk._getSpecLinkNormalSizeMono();} document.head.appendChild(el);

1.  GENERAL

If you have pre-customised this work section using the “questions and answers” provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.

The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.

This section relates to the supply and fixing of KOROK® steel clad, lightweight aerated concrete (AC) fire and acoustically rated panels, as a non-load bearing inter-tenancy wall system.

The system is a proprietary high-performance wall that provides horizontal fire and acoustic separation between adjacent tenancies in the same building. The KOROK® Inter-tenancy System is suitable for use in medium and high-density housing, i.e. terraced housing and commercial multi-tenancy units. Modify or extend the above description to suit the project being specified.

1.1 RELATED WORK

  • Refer to 4259KE KOROK® EXTERIOR WALL SYSTEMS section for exterior wall cladding.
  • Refer to 5216S KOROK® COMMERCIAL INTERIOR WALL SYSTEMS section for interior walls other than inter-tenancy walls.
  • Refer to 3421 LIGHT STEEL FRAMED BUILDINGS section for light weight steel support structure.
  • Refer to 5113G GIB® PLASTERBOARD LININGS section for finishing and stopping of plasterboard linings.

The section(s) stated above are often necessary to support this section, consider carefully and ensure they are included in the project specification if required. Include cross references to other sections where these contain related work. These may include timber and steel framing sections, insulation sections and plasterboard lining sections.

1.2 ABBREVIATIONS AND DEFINITIONS

Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.

The following abbreviations apply specifically to this section:

KOROK® KOROK® Building Systems NZ Ltd.
BMT Base metal thickness
AC Lightweight aerated concrete
FRR Fire Resistance Rating
STC Sound transmission class

The following definitions apply specifically to this section:

KIT KOROK® Intertenancy Terraced Housing
KIM KOROK® Intertenancy Apartments
KIR KOROK® Intertenancy Apartments with Ceiling

 

Documents

1.3 DOCUMENTS

Refer to the general section 1233 REFERENCED DOCUMENTS. The following documents are specifically referred to in this section:

NZBC C/AS2                     Protection from fire for buildings other than risk group SH

NZBC G6                            Airborne and impact sound

NZS 1170.5                       Structural design actions – Earthquake actions – New Zealand

AS 1397                             Continuous hot-dip metallic coated steel sheet and strip – Coatings of zinc and zinc alloyed with aluminium and magnesium

AS 1538                             Cold formed steel structures code

AS/NZS 2589                   Gypsum linings – Application and finishing

NZS 3604                          Timber framed buildings

Delete from the DOCUMENTS clause any document not cited. List any additional cited documents.

The following are related documents and if referred to in the work section need to be added to the list of DOCUMENTS

BPS                                      Building Product Specifications

NZBC C/AS1                     Protection from fire for buildings with sleeping (residential) and outbuildings (risk group SH)

NZBC E2/AS1                   External moisture provisions for timber-framed buildings up to 10 m in height

AS 1530.4:2005              Methods for fire tests on building materials, components and structures – Fire-resistance test of elements of construction

AS 3404.1                          Steel Structures Standard

AS 3715                             Metal finishing – Thermoset powder coatings for architectural applications

BRANZ BU 369                Fitting tolerances

BRANZ BU 519                Fasteners selection

BRANZ BU 531                Providing for thermal and moisture movement

NZS 3602                          Timber and wood-based product for use in building

NZS 7202.1                       Specification for gap filling adhesives

WorkSafe                           Guidelines for the provision of facilities and general safety in the construction industry

AS 1530.4:2005 is referenced in NZBC C/AS1-AS2 at the time of writing. AS 1530.4:2014 is the current version but is not cited in the NZBC.

1.4 MANUFACTURER/SUPPLIER DOCUMENTS

Manufacturer’s and supplier’s documents related to this section are:

List documents relating to this part of the work, i.e. technical product/system specifications, test reports, appraisals, certification, etc. Normally they will be referred to in the text by the abbreviated title.

Manufacturer/supplier contact details

Company:                         KOROK®Building Systems NZ Ltd.

Web:                                   www.korok.com

Email:                                 info@korok.com

Phone:                                0800 773 777

It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project. In most cases individual products are not used in isolation, but form part of a building process. Also a particular manufacturer’s and/or supplier’s requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm. Access to technical information can help overcome this potential problem.

 

Warranties

Use for listing all warranties relating to this section. Supplier and manufacturer warranties are those that are freely offered by the supplier or manufacturer, similarly installers and applicators. They are usually in their standard form and subject to their terms and conditions. Check the general section 1237 WARRANTIES for the date of commencement of warranties; which is normally Practical Completion of the contract, although not all suppliers, manufacture’s, installers or applicators will agree to this. Refer to the chosen conditions of contract as it may also contain information on warranties.

1.5  WARRANTY – MANUFACTURER/SUPPLIER

Provide a material manufacturer/supplier warranty:

15 years: For KOROK® materials

Refer to KOROK® Building Systems NZ Ltd. for details of Materials Warranty.

  •  Provide this warranty on theKOROK® standard form (if unavailable, use the standard form in the general section 1237WA WARRANTY AGREEMENT)
  •  Commence the warranty from the date of Practical Completion of the contract works.

Refer to the general section 1237 WARRANTIES for additional requirements.

Modify or expand the clause to suit project or manufacturer/supplier requirements, eg:

  •  Modify the form to be used
  •  Commence the warranty from the date of purchase (check with the manufacturer/supplier)

1.6 WARRANTY – INSTALLER/APPLICATOR

Provide an installer/applicator warranty:

2 years: For workmanship

  •  Provide this warranty on the installer/applicator standard form (if unavailable, use the standard form in the general section 1237WA WARRANTY AGREEMENT)
  •  Commence the warranty from the date of Practical Completion of the contract works.

Refer to the general section 1237 WARRANTIES for additional requirements.

Modify or expand the clause to suit project requirements, options include:

  • Commence the warranty from the date of completion of this part of the contract work

Requirements

1.7 QUALIFICATIONS GENERALLY

Refer to the general section 1270 CONSTRUCTION for requirements relating to qualifications.

1.8 ACCEPTABLE PRODUCT/MATERIAL SUPPLIERS

Where a product or material supplier is named in SELECTIONS, the product/material must be provided by the named supplier. Where there is more than one named supplier, any one of the named suppliers will be acceptable. Refer to other manufacturers details for specific information on their products.

This clause is used to nominate a supplier or suppliers to supply materials. It is not intended for nominating subcontractors which must be done in the specific conditions of contract applying to the work. Check with BCA for acceptability of multiple selection options.

Modify this clause to suit project requirements. Add references to other sections in the specification as appropriate.

1.9 NO SUBSTITUTIONS

Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.

1.10 INFORMATION FOR OPERATION AND MAINTENANCE

Where KOROK® panels are exposed, an inspection should be carried out at least annually to ensure that no undue degradation is occurring. Where corrosion is identified, the cause must be determined and repairs made to restore the integrity of the system.

Where KOROK® panels are not exposed, no maintenance should be required. Damage to linings or claddings should be repaired immediately.

Performance

Note that in using the next clause you are setting a standard of performance for the contractor to meet. Specifiers should therefore consider adding some means of confirming (e.g.by testing or certification) that the performance criteria will be or have been met.

1.11 NOISE CONTROL TESTS

KOROK® noise control testing and results were found to be satisfactory by BRANZ for NZBC G6/AS1 as noted in BRANZ Appraisal 559 – KOROK® FS & NCS Systems and BRANZ Appraisal 1059 – KOROK® 51mm Wall Systems.

It is important to consider the requirements for the acoustic design of any surrounding systems; their performance must be at least equivalent to that required of the panels themselves.

1.12 SURFACE FIRE PROPERTIES FOR LININGS

Group Number to NZBC C/AS2, Table 4.12.1.1: Maximum permitted Group Number for internal surface finishes. Refer to SELECTIONS.

NOTE: For most internal applications a surface fire performance Group Number will be required to NZBC C/AS2, Table 4.12.1.1: Maximum permitted Group Number for internal surface finishes (services to Table 4.12.6.2: Maximum permitted Group Number for the surfaces of building services). If the Group number is established from BPS, Table 8.5.2.1: Material Group Numbers for some substrate and coating combinations, modify the clause.

Delete clause if not required. A Group Number may not be required in situations such as, the surface area is less than 5m² (NZBC C/AS2, paragraph 4.12.4.1 (a)), or the design is to NZBC C/AS1 risk group SH (houses etc).

Compliance Information

1.13 INFORMATION REQUIRED FOR CODE COMPLIANCE

Provide the following compliance documentation: –

  • Installer’s approval certificate from the product manufacturer / importer / distributor
  • Manufacturer / supplier warranty
  • Installer / applicator warranty
  • Producer Statement – Construction (PS3) from the applicator / installer
  • Producer Statement – Construction Review (PS4) from a suitably qualified person
  • Other information required by the BCA in the Building Consent Approval

List the Producer Statements – Construction (PS3) required from installers that are required as a condition of carrying out this work.

List also Producer Statements – Construction Review (PS4) required from consultants to be engaged by the Contractor.

Producer Statement – Design (PS1), may be required where certain design work is undertaken by the Contractor or manufacturer / importer / distributor.

Quality control and assurance

1.14 INSPECTIONS

Allow to inspect the whole of the work at each stage. Determine a programme for inspections including notification when each part and stage of the work is ready for inspection prior to the work commencing. Permit representatives of KOROK® to inspect the work in progress and to take samples of their product from site if requested. Refer to KOROK® Technical and Installation Manual.

Use this clause for parts of the work where;

Special arrangements are required for notification for inspections.

These inspections may include ‘Hold Points’ or ‘Notification Points’. Refer to 1232 INTERPRETATION & DEFINITIONS for complete definitions.

Hold Point:                         Work may not proceed until the work in question has been inspected.

Notification Point:           Notify Contract Administrator, work may be observed or not, work may proceed.

or

the manufacturer/supplier is required to carry out inspections outside their normal activities and provide reports or other documents in support of the work carried out.

or

the Contractor is required to carry out or engage consultants to carry out inspections of parts of the work. It will typically be expected that the person carrying out the inspections will be required to provide producer statements in support of the work carried out.

2.  PRODUCTS

Materials – general

2.1 KOROK® PANELS

Tongue-&-groove jointed cold roll formed steel shells to AS 1538 and galvanized to AS 1397, filled with proprietary aerated concrete infill. Paint coated steel coil can also be used on one or both sides.

Panel size nominal:           250mm wide, 51mm or 78mm thick

Panel length:                       made to measure up to 9.4m (78mm Gen2); 9.0m (78mm Gen1); 5.0 (51mm)

Panel density:                     400kg/m³, 600kg/m³, 800kg/m³ or 1000kg/m³

Metal thickness:                0.4mm BMT

Modify this clause to suit project requirements. Custom panel lengths can be made up to 9.0m but panel spans for fire rated systems are generally limited to a maximum of 6.0m, unless specifically designed. Standard panel density is 600kg/m3 for 51mm panel and 400kg/m³ for 78mm panel. Refer to KOROK® Building Systems NZ Ltd for further information.

2.2 KOROK® TRACKS

KOROK® ‘C-track’ and KOROK® Angle, cold roll formed steel to AS 1538 and galvanized to AS 1397, form the edges and perimeters of the panels. May be powder coated.

C-track:                              60mm x 80mm web

Angle:                                  60mm x 60mm

Metal thickness:              1.15mm BMT

Track length:                      up to 3.6m.

Refer to KOROK® Manuals for fixing details

2.3 KOROK® FIRE FLASHING

KOROK® Fire Flashing, cold roll formed steel to AS 1538 and galvanized to AS 1397, used as part of the head detail for the KOROK® fire rated systems.

Fire Flashing:                     110mm

Metal thickness:                0.55mm BMT

Track length:                      up to 3.6m.

Refer to KOROK® Manuals for fixing details

2.4 KOROK® KIT FLASHING

KOROK® KIT Flashing, cold roll formed steel to AS 1538 and galvanized to AS 1397, used as part of the horizontal joint detail for the KOROK® fire rated systems.

KIT Flashing:                      160mm

Metal thickness:                0.55mm BMT

Track length:                      up to 3.6m.

Refer to KOROK® Manuals for fixing details

Components

Modify the following component clauses to more accurately describe the project design.

2.5 SCREW FIXINGS

Self-drilling, self-tapping to suit the member, connection method and location. Refer to KOROK® manuals for fixing details and the fixing manufacturers information.

Location Type
C-track to concrete
C-track to steel Hilti® X DN1 16MX nail
Track to panel 10×16 and 10×30 galvanized Steeltite™ wafer head screws
Panel to panel 10×16 and 10×30 galvanized Steeltite™ wafer head screws

Refer to KOROK® Manuals for fixing details

2.6 POWDER ACTUATED FASTENERS

To type, size and charge required by the powder actuated tool manufacturer, to suit the member, connection method and location. Refer to KOROK® Technical and Installation Manual, and the fixing manufacturer’s printed data.

Refer to KOROK® manuals for fixing details

2.7 FIRE SEALANT

KOROK® Fire Rated Sealant – Sikaflex® 400, Hilti® CP606 or PROMASEAL-A®

Consult with KOROK® Building Systems NZ Ltd if excessive movement is anticipated.

 

Accessories

2.8 LIGHT STEEL FRAMING

To NASH Standard Part 2, Appendix D. Member Classifications and section 2. Materials & Members. Cold roll formed steel sections galvanized to AS 1397. Refer to 3421 LIGHT STEEL FRAMED BUILDINGS.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS.

2.9 TIMBER FRAMING

Timber framing to NZS 3604. Refer to 3821 TIMBER FRAMING.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS.

2.10 GIB® PLASTERBOARD LINING

Gypsum plaster core encased in a face and backing paper formed for standard and water resistance use to AS/NZS 2588. Refer to 5113G GIB PLASTERBOARD LININGS and 5171G GIB PLASTERBOARD FIRE & SOUND BOARD.

Refer to KOROK® manuals for fixing details.

2.11 PINK BATTS INSULATION

Pink® Batts® Silencer® bio-soluble glass wool manufactured from up to 80% recycled glass in slabs and coloured grey for identification. Refer to 4710P PINK® BATTS® THERMAL & ACOUSTIC INSULATION.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS

2.12 GREENSTUF® POLYESTER FIBRE MASONRY WALL ACOUSTIC BLANKET INSULATION

GreenStuf® Masonry Wall Blanket – 100% polyester fibres thermally bonded to form a flexible blanket/roll for thermal insulation and control of sound transmission in strapped and lined masonry walls. Refer to 4721AG AUTEX GREENSTUF ACOUSTIC INSULATION.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS

2.13 GREENSTUF® SOUND SOLUTION® PLUS INSULATION

Acoustic insulation blanket used as ceiling overlay in commercial applications or for intertenancy walls. Refer to 4721AG AUTEX GREENSTUF ACOUSTIC INSULATION.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS

2.14 BRADFORD ACOUSTIGARD™ INSULATION

Bradford™ Acoustigard™ Partition Blanket Lightweight acoustic blanket. Refer to 4721B BRADFORD® ACOUSTIC INSULATION.

Delete/modify if specified in another section or if not required. Refer to SELECTIONS

3.  EXECUTION

Conditions

3.1 DELIVERY, STORAGE & HANDLING OF PRODUCTS

Refer to 1270 CONSTRUCTION for requirements relating to delivery, storage and handling of products.

Use this standard generic clause and if appropriate add special requirements.

3.2 ROUTINE MATTERS

Refer to the general section 1250 TEMPORARY WORKS & SERVICES for protection requirements. Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.

Use this standard generic clause and if appropriate add special requirements.

3.3 SUBSTRATE

Carry out all necessary inspections and preparatory work to the supporting elements of the KOROK® Inter-tenancy System prior to installation. Do not commence work until the framing is plumb, level and to the standard required by AS/NZS 2589 and KOROK® Inter-tenancy System requirements.

3.4 TIMBER FRAME MOISTURE CONTENT

Maximum allowable moisture content to AS/NZS 2589 Gypsum linings – Application and finishingfor timber framing at lining: 18% or less for plasterboard linings.

3.5 STANDARDS AND TOLERANCES

Refer to the general section 1270 CONSTRUCTION for general requirements.

Amend this clause to describe specific standards and tolerances to be achieved in carrying out this part of the work. Although such tolerances are typically included in standards (NZS, AS/NZS, etc.) in certain circumstances it is worth restating these in this clause.

3.6 FIXINGS – EARTHQUAKE

Use fixings and methods capable of sustaining the loads appropriate to the earthquake zone as required by NZS 1170.5 Structural design actions – Earthquake actions.

This clause might only apply where the method of fixing the panels is required, by design or regulation, to comply with the earthquake requirements of NZS 1170.

3.7 SOUND RATING

Refer to KOROK® Inter-tenancy System literature for correct forming and treating of penetrations, to ensure the specified acoustic performance is met. Ensure absence of adjoining flanking paths.

 

Installation: KOROK Systems

3.8 INSTALL PANELS

Install KOROK® panels in accordance with the KOROK® Intertenancy Systems Manual.

3.9 FIX KOROK® FIRE FLASHING

Install KOROK® fire flashing to top C-track, in accordance with the KOROK® Intertenancy Systems Manual.

3.10 FIX KOROK® KIT FLASHING

Install KOROK® kit flashing to horizontal joints, in accordance with the KOROK® Intertenancy Systems Manual.

3.11 ALIGNMENT OF FRAMING

To the standard required by KOROK®, plumb, level and in true alignment.

Use this standard generic clause and if appropriate add special requirements.

3.12 FIRE REQUIREMENTS

To maintain fire rating and integrity of the areas noted as ‘fire rated’ on the drawings between residential units, comply with all relevant aspects of the KOROK® Inter-tenancy System literature according to the fire resistance rating (FRR) and other relevant product manufacturers’ recommendations.

3.13 SERVICES

Piped and cabled services within KOROK® Inter-tenancy System framing cavities to be securely fastened to the framing, and must not be in contact with, or pass through, the central barrier. Minimum 10mm clearance must be provided between any plumbing or electrical services and the central barrier.

3.14 ACOUSTIC REQUIREMENTS

To maintain acoustic integrity of the areas noted as ‘sound rated’ on the drawings, comply with all relevant aspects of the KOROK® Intertenancy System literature according to the specified sound transmission class (STC) rating and other relevant product manufacturers’ recommendations.

3.15 PENETRATIONS

Under no circumstances should any services penetrate the KOROK® Intertenancy System panels unless approved by a Fire Engineer. Services may however be concealed within the framed section of the wall system, subject to the following constraints:

  • Minimum of 10mm clearance to be maintained between any penetrations and the central
  • Penetrations to be no larger than 65mm diameter or 90mm x 50mm through the plasterboard There is no requirement to firestop these penetrations.
  • No more than two penetrations per 600mm bay of framing to be

3.16 PRIMING STEEL

Use either Resene Galvo-Prime or Zinc rich spray primer to ensure that all exposed steel has been spot primed.

Available from KOROK® or Resene Color Shops, or other selected merchants. Refer to relevant Resene documents for application.

 

Finishing: general

3.17 FINISHING AND STOPPING

Refer to and AS/NZS 2589 Gypsum liningsand 5113G GIB® PLASTERBOARD LININGS section for finishing and stopping of plasterboard linings.

Completion & Commissioning

3.18 Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.

Use this standard generic clause and if appropriate add special requirements.

3.19 COMPLETION – TESTS & CERTIFICATION

Refer to the general section 1270 CONSTRUCTION for general test and certification requirements at completion.

Expand this clause to detail specific requirements for tests and certification required on completion of this section of work. For example acoustic tests, thermal testing, leak testing etc. Nominate the person that test results and / or certification is to be submitted to. Co-ordinate with the INSPECTIONS clause if required to link testing with a Hold Point or Notification Point. Delete this clause if there are no testing / certification requirements.

4.  SELECTIONS

For further details on selections go to www.korok.com.

Substitutions are not permitted to the following KOROK® materials or components, unless stated otherwise.

If substitutions are permitted modify the statement above, ensure the NO SUBSTITUTIONS clause from GENERAL is treated the same.

Select the options to suit the project and delete options not specified.

 

KOROK® KIM Apartment Inter-tenancy Systems (FRR-/60/60)

4.1 KOROK® KIM01 INTER-TENANCY SYSTEM

  • Location:                                     ~
  • Wall thickness:                         194mm
  • Panel:                                            51mm
  • Density:                                       600Kg/m³
  • STC:                                               58
  • FRR:                                               -/60/60
  • Cavity:                                           Min 20mm
  • Lining side #1:                            1x layer 13mm GIB® Standard
  • Lining side#2:                              1x layer 13mm GIB® Standard
  • Frame side #1:                             64mm steel frame
  • Frame side #2:                             28mm furring channel on direct fix clips
  • Acoustic insulation side #1:       ~
  • Acoustic insulation side #2:     Autex R0.5 GreenStuf® Masonry Wall Blanket 20mm

Acoustic insulation side #1    GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartment Systems manual for fixing details

4.2 KOROK® KIM02 INTER-TENANCY SYSTEM

  • Location:                                    ~
  • Wall thickness:                       122mm
  • Panel:                                          51mm
  • Density:                                     600Kg/m³
  • STC:                                             57
  • FRR:                                             -/60/60
  • Cavity:                                         None
  • Lining side #1:                          1x layer 13mm GIB Noiseline®
  • Lining side #2:                           1x layer 13mm GIB Noiseline®
  • Frame side #1:                           28mm furring channel on GIB® ST-001 resilient mounts
  • Frame side #2:                           None
  • Acoustic insulation side #1:  R1.3 GreenStuf® Masonry Wall Blanket 45mm
  • Acoustic insulation side #2:  None

Resilient mounts fixed @ 1000mm centres to furring channel fixed @ 600mm centres to KOROK® panels Refer to KOROK® Intertenancy Apartment Systems manual for fixing details.

4.3 KOROK® KIM03 INTER-TENANCY SYSTEM

  • Location:                                 ~
  • Wall thickness:                     167mm
  • Panel:                                       51mm
  • Density:                                   600Kg/m³
  • STC:                                           59
  • FRR:                                          -/60/60
  • Cavity:                                       None
  • Lining side #1:                        1x layer 13mm GIB Noiseline®
  • Lining side #2:                         1x layer 13mm GIB Noiseline®
  • Frame side #1:                         28mm furring channel on GIB® ST-001 resilient mounts
  • Frame side #2:                          28mm furring channel on GIB® ST-001 resilient mounts
  • Acoustic insulation side #1:  R1.3 GreenStuf® Masonry Wall Blanket 45mm 
  • Acoustic insulation side #2:  R1.3 GreenStuf® Masonry Wall Blanket 45mm

Resilient mounts fixed @ 1000mm centres to furring channel fixed @ 600mm centres to KOROK® panels

Refer to KOROK® Intertenancy Apartment Systems Manual for fixing details.

4.4 KOROK® KIM04 INTER-TENANCY SYSTEM

  • Location:                                     ~
  • Wall thickness:                        161mm
  • Panel:                                          51mm
  • Density:                                      600Kg/m³
  • STC:                                              59
  • FRR:                                             -/60/60
  • Cavity:                                         Min 20mm
  • Lining side #1:                          1x layer 13mm GIB® Standard
  • Lining side #2:                          1x layer 13mm GIB® Standard
  • Frame side #1:                         64mm steel frame
  • Frame side #2:                         None
  • Acoustic insulation side #1:   ~
  • Acoustic insulation side #2:  None

Acoustic insulation side #1 GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartment Systems manual for fixing details

4.5 KOROK® KIM05 INTER-TENANCY SYSTEM

  • Location:                               ~
  • Wall thickness:                   240mm
  • Panel:                                     51mm
  • Density:                                600Kg/m³
  • STC:                                        68
  • FRR:                                        -/60/60
  • Cavity:                                   Min 86mm between framing – Note: Framing not to touch KOROK® panel.
  • Lining side #1:                    1x layer 13mm GIB® Standard
  • Lining side #2:                    1x layer 13mm GIB® Standard
  • Frame side #1:                    64mm steel frame
  • Frame side #2:                    64mm steel frame
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: ~

Acoustic insulation side #1 GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Acoustic insulation side #2 GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8.

Refer to KOROK® Intertenancy Apartment Systems manual for fixing details

4.6 KOROK® KIM08 INTER-TENANCY SYSTEM

  • Location:                                  ~
  • Wall thickness:                      181mm
  • Panel:                                         51mm
  • Density:                                     600Kg/m³
  • STC:                                            61
  • FRR:                                            -/60/60
  • Cavity:                                        Min 20mm between panel and frame
  • Lining side #1:                         1x layer 13mm GIB Noiseline®
  • Lining side #2:                         1x layer 13mm GIB Noiseline®
  • Frame side #1:                         64mm steel frame
  • Frame side #2:                         16mm furring channel on Rondo® BetaGrip® clips
  • Acoustic insulation side #1: Bradford 75mm acoustigard™ 14Kg/m³
  • Acoustic insulation side #2:  None

Furring channels @ 600mm centres

Rondo® BetaGrip® clips @ max. 1000mm centres

Refer to KOROK® Intertenancy Apartment Systems Manual for fixing details.

4.7 KOROK® KIM09 INTER-TENANCY SYSTEM

  • Location:                                  ~
  • Wall thickness:                      175mm
  • Panel:                                        51mm
  • Density:                                    600Kg/m³
  • STC:                                           60
  • FRR:                                            -/60/60
  • Cavity:                                        None
  • Lining side #1:                         1x layer 13mm GIB Noiseline®
  • Lining side #2:                         1x layer 13mm GIB Noiseline®
  • Frame side #1:                         28mm furring channel on Rondo® BetaGrip® clips
  • Frame side #2:                          28mm furring channel on Rondo® BetaGrip® clips
  • Acoustic insulation side #1:  Pink Batts® R1.2 50mm 12.8kg/m³
  • Acoustic insulation side #2:   Pink Batts® R1.2 50mm 12.8kg/m³

Furring channel @ 600mm centres

Rondo® BetaGrip® clips @ max. 600mm centres

Refer to KOROK® Intertenancy Apartment Systems Manual for fixing details.

4.8 KOROK® KIM12 INTER-TENANCY SYSTEM

  • Location:                                  ~
  • Wall thickness:                      167mm
  • Panel:                                         51mm
  • Density:                                     600Kg/m³
  • STC:                                             61
  • FRR:                                             -/60/60
  • Cavity:                                         Min 10mm
  • Lining side #1:                          1x layer 13mm GIB Noiseline®
  • Lining side #2:                          1x layer 13mm GIB Noiseline®
  • Frame side #1:                          64mm steel frame
  • Frame side #2:                          6mm furring channel directly fixed (no clips)
  • Acoustic insulation side #1: Bradford 75mm acoustigard™ 14Kg/m³
  • Acoustic insulation side #2: None

Furring channels @ 600mm centres

Refer to KOROK® Intertenancy Apartment Systems Manual for fixing details.

4.9 KOROK® KIM13 INTER-TENANCY SYSTEM

  • Location:                                    ~
  • Wall thickness:                      194mm
  • Panel:                                         51mm
  • Density:                                     600Kg/m³
  • STC:                                             64
  • FRR:                                             -/60/60
  • Cavity:                                         Min 20mm
  • Lining side #1:                          2x layers 13mm GIB Noiseline®
  • Lining side #2:                          1x layer 13mm GIB Noiseline®
  • Frame side #1:                          64mm steel frame
  • Frame side #2:                          16mm furring channel on direct fixed Rondo® 237 clips
  • Acoustic insulation side #1: Bradford 75mm acoustigard™ 14Kg/m³
  • Acoustic insulation side #2: None

Furring channels @ 600mm centres

Refer to KOROK® Technical and Installation Manual for fixing details.

KOROK® KIM Inter-tenancy Apartment Systems (FRR -/120/120)

4.10KOROK® KIM06 INTER-TENANCY SYSTEM

  • Location:                                   ~
  • Wall thickness:                      188mm
  • Panel:                                        78mm
  • Density:                                    400Kg/m³
  • STC:                                            59
  • FRR:                                            -/120/120
  • Cavity:                                       Min 20mm between panel and frame
  • Lining side #1:                       1x layer 13mm GIB Noiseline®
  • Lining side #2:                        1x layer 13mm GIB® Standard
  • Frame side #1:                        64mm steel frame
  • Frame side #2:                          None
  • Acoustic insulation side #1:   ~
  • Acoustic insulation side #2:  None

Acoustic insulation side #1    GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartment Systems manual for fixing details

4.11 KOROK® KIM07 INTER-TENANCY SYSTEM

  • Location:                                       ~
  • Wall thickness:                          188mm
  • Panel:                                            78mm
  • Density:                                        400Kg/m³
  • STC:                                                59
  • FRR:                                                -/120/120
  • Cavity:                                           Min 20mm between panel and frame
  • Lining side #1:                            1x layer 13mm GIB® Standard\
  • Lining side #2:                            1x layer 13mm GIB® Standard
  • Frame side #1:                           64mm steel frame
  • Frame side #2:                           None
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: None

Acoustic insulation side #1     GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartment Systems manual for fixing details

 

KOROK® KIT Terraced Housing Inter-tenancy Systems (FRR 60/60/30)

4.12 KOROK® KIT01A INTER-TENANCY SYSTEM

  • Location:                                  ~
  • Wall thickness:                     288mm
  • Panel:                                        51mm
  • Density:                                    600Kg/m³
  • STC:                                            64
  • FRR:                                            60/60/30
  • Cavity:                                        Min 86mm overall
  • Lining side #1:                         1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                         1x layer 10mm GIB® Standard plasterboard
  • Frame side #1:                          ~
  • Frame side #2:                          ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                   90mm timber frame, or 90mm steel frame

Acoustic insulation side #1    GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2   GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

KOROK® KIT Inter-tenancy Terraced Housing Systems (FRR 60/60/60)

4.13 KOROK® KIT01 INTER-TENANCY SYSTEM

  • Location:                                 ~
  • Wall thickness:                    288mm
  • Panel:                                       51mm
  • Density:                                  600Kg/m³
  • STC:                                          64
  • FRR:                                          60/60/60
  • Cavity:                                      Min 86mm overall
  • Fire flashing:                           required
  • Kit flashing:                             required
  • Lining side #1:                       1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                        1x layer 10mm GIB® Standard plasterboard
  • Frame side #1:                         ~
  • Frame side #2:                          ~
  • Acoustic insulation side #1: ~
  • Acoustic insulation side  #2: ~

Frame side #1            90mm timber frame, or 90mm steel frame

Frame side #2            90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.14 KOROK® KIT01 MODIFIED INTER-TENANCY SYSTEM

  • Location:                                   ~
  • Wall thickness:                      282mm
  • Panel:                                         51mm
  • Density:                                    600Kg/m³
  • STC:                                            63
  • FRR:                                            60/60/60
  • Cavity:                                       Min 80mm overall
  • Fire flashing:                            required
  • Kit flashing:                              required
  • Lining side #1:                        1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                        1x layer 10mm GIB® Standard plasterboard
  • Frame side #1:                           ~
  • Frame side #2:                           ~
  • Acoustic insulation side  #1: ~
  • Acoustic insulation side #2: ~

Frame side #1         90mm timber frame, or 90mm steel frame

Frame side #2        90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.15 KOROK® KIT02 INTER-TENANCY SYSTEM

  • Location:                                  ~
  • Wall thickness:                    288mm
  • Panel:                                       51mm
  • Density:                                  600Kg/m³
  • STC:                                          66
  • FRR:                                          60/60/60
  • Cavity:                                       Min 86mm overall
  • Fire flashing:                           required
  • KIT flashing:                            required
  • Lining side #1:                        1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                        1x layer 10mm GIB Noiseline® plasterboard
  • Frame side #1:                         ~
  • Frame side #2:                          ~
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: ~

Frame side #1     90mm timber frame, or 90mm steel frame

Frame side #2      90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.16 KOROK® KIT03 INTER-TENANCY SYSTEM

  • Location:                               ~
  • Wall thickness:                   288mm
  • Panel:                                     51mm
  • Density:                                 600Kg/m³
  • STC:                                        67
  • FRR:                                        60/60/60
  • Cavity:                                   Min 86mm overall
  • Fire flashing:                        required
  • KIT flashing:                         required
  • Lining side #1:                    1x layer 10mm GIB Noiseline® plasterboard
  • Lining side #2:                    1x layer 10mm GIB Noiseline® plasterboard
  • Frame side #1:                     ~
  • Frame side #2:                     ~
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                    90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.17 KOROK® KIT04 INTER-TENANCY SYSTEM

  • Location:                               ~
  • Wall thickness:                   294mm
  • Panel:                                     51mm
  • Density:                                600Kg/m³
  • STC:                                       69
  • FRR:                                       60/60/60
  • Cavity:                                  Min 86mm overall
  • Fire flashing:                      required
  • KIT flashing:                       required
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB Noiseline® plasterboard
  • Frame side #1:                   ~
  • Frame side #2:                    ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                  90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.18 KOROK® KIT05 INTER-TENANCY SYSTEM

  • Location:                    ~
  • Wall thickness:        294mm
  • Panel:                          51mm
  • Density:                      600Kg/m³
  • STC:                             66
  • FRR:                             60/60/60
  • Cavity:                        Min 86mm overall
  • Fire flashing:            required
  • KIT flashing:             required
  • Lining side #1:        1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:        1x layer 13mm GIB® Standard plasterboard
  • Frame side #1:         ~
  • Frame side #2:        ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                    90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

KOROK® KIT Inter-tenancy Terraced Housing Systems (FRR 120/120/120)

4.19 KOROK® KIT06 INTER-TENANCY SYSTEM

  • Location:                              ~
  • Wall thickness:                   315mm
  • Panel:                                     78mm
  • Density:                                400Kg/m³
  • STC:                                       65
  • FRR:                                       120/120/120
  • Cavity:                                   Min 113mm overall
  • Fire flashing:                      required
  • KIT flashing:                       required
  • Lining side #1:                  1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                 1x layer 10mm GIB® Standard plasterboard
  • Frame side #1:                  ~
  • Frame side #2:                  ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                   90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.20 KOROK® KIT07 INTER-TENANCY SYSTEM

  • Location:                              ~
  • Wall thickness:                  315mm
  • Panel:                                    78mm
  • Density:                               400Kg/m³
  • STC:                                      66
  • FRR:                                      120/120/120
  • Cavity:                                Min 113mm overall
  • Fire flashing:                   required
  • KIT flashing:                    required
  • Lining side #1:               1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:               1x layer 10mm GIB Noiseline® plasterboard
  • Frame side #1:                  ~
  • Frame side #2:                  ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                   90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.21 KOROK® KIT08 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                315mm
  • Panel:                                 78mm
  • Density:                            400Kg/m³
  • STC:                                   67
  • FRR:                                  120/120/120
  • Cavity:                              Min 113mm overall
  • Fire flashing:                   required
  • KIT flashing:                    required
  • Lining side #1:               1x layer 10mm GIB Noiseline® plasterboard
  • Lining side #2:               1x layer 10mm GIB Aqualine® (wet) or 10mm GIB Noiseline® (dry) plasterboard
  • Frame side #1:                  ~
  • Frame side #2:                  ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                  90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

4.22 KOROK® KIT10 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                321mm
  • Panel:                                 78mm
  • Density:                            400Kg/m³
  • STC:                                   67
  • FRR:                                  120/120/120
  • Cavity:                              Min 113mm overall
  • Fire flashing:                  required
  • KIT flashing:                   required
  • Lining side #1:               1x layer 13mm GIB® Standard plasterboard (or equivalent)
  • Lining side #2:               1x layer 13mm GIB® Standard plasterboard (or equivalent)
  • Frame side #1:                 ~ 
  • Frame side #2:                 ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                  90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

 

KOROK® KIT Inter-tenancy Terraced Housing Systems (FRR 120/120/60)

4.23 KOROK® KIT06A INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                315mm
  • Panel:                                  78mm
  • Density:                              400Kg/m³
  • STC:                                      65
  • FRR:                                      120/120/60
  • Cavity:                                  Min 113mm overall
  • Lining side #1:                   1x layer 10mm GIB® Standard plasterboard
  • Lining side #2:                   1x layer 10mm GIB® Standard plasterboard
  • Frame side #1:                    ~
  • Frame side #2:                    ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                   90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details Refer to KOROK® Technical and Installation Manual for fixing details.

4.24 KOROK® KIT09 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                321mm
  • Panel:                                  78mm
  • Density:                              400Kg/m³
  • STC:                                      69
  • FRR:                                      120/120/60
  • Cavity:                                 Min 113mm overall
  • Lining side #1:                 1x layer 13mm GIB Noiseline® plasterboard (or equivalent)
  • Lining side #2:                 1x layer 13mm GIB Aqualine® (wet) or 13mm GIB Noiseline® (dry) plasterboard
  • Frame side #1:                  ~
  • Frame side #2:                  ~
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Frame side #1                   90mm timber frame, or 90mm steel frame

Frame side #2                   90mm timber frame, or 90mm steel frame

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Acoustic insulation side #2  GreenStuf® Sound Solution® Plus 90, or 90mm Pink Batts® R2.2

Refer to KOROK® Intertenancy Terraced Housing Systems manual for fixing details

 

KOROK® KIR Inter-tenancy Apartments with ceiling Systems (FRR-/60/60)

4.25 KOROK® KIR01 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                194mm
  • Panel:                                   51mm
  • Density:                              600Kg/m³
  • STC:                                      58
  • FRR:                                      -/60/60
  • Cavity:                                Min 20mm
  • Lining side #1:                 1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:                 1x layer 13mm GIB® Standard plasterboard Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                 64mm Steel frame
  • Frame side #2:                 28mm Furring channel on direct fix clips
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: R0.5 GreenStuf® Masonry Wall Blanket 20mm

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 75, or Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.26 KOROK® KIR02 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:               122mm
  • Panel:                                  51mm
  • Density:                             600Kg/m³
  • STC:                                      57
  • FRR:                                      -/60/60
  • Cavity:                                 N/A
  • Lining side #1:                 1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                 1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on resilient mounts
  • Frame side #2:                   N/A
  • Acoustic insulation side #1:  R1.3 GreenStuf® Masonry Wall Blanket 45mm 
  • Acoustic insulation side #2: N/A

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.27 KOROK® KIR03 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                 167mm
  • Panel:                                   51mm
  • Density:                               600Kg/m³
  • STC:                                      59
  • FRR:                                       -/60/60
  • Cavity:                                  N/A
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on resilient mounts
  • Frame side #2:                  28mm Furring channel on resilient mounts
  • Acoustic insulation side #1: R1.3 GreenStuf® Masonry Wall Blanket 45mm
  • Acoustic insulation side #2: R1.3 GreenStuf® Masonry Wall Blanket 45mm

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.28 KOROK® KIR04 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                161mm
  • Panel:                                  51mm
  • Density:                             600Kg/m³
  • STC:                                    59
  • FRR:                                   -/60/60
  • Cavity:                               Min 20mm
  • Lining side #1:                1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:                1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm Steel frame
  • Frame side #2:                  N/A
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2: N/A

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.29 KOROK® KIR05 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                240mm
  • Panel:                                  51mm
  • Density:                             600Kg/m³
  • STC:                                     68
  • FRR:                                     -/60/60
  • Cavity:                                Min 86mm between framing – Note: Framing not to touch KOROK® panel.
  • Lining side #1:                  1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:                  1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm Steel frame
  • Frame side #2:                  64mm Steel frame
  • Acoustic insulation side #1:  ~
  • Acoustic insulation side #2:  ~

Acoustic insulation side #1         GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Acoustic insulation side #2       GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.30 KOROK® KIR08 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                181mm
  • Panel:                                   51mm
  • Density:                              600Kg/m³
  • STC:                                      61
  • FRR:                                      -/60/60
  • Cavity:                                 Min 20mm
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm Steel frame
  • Frame side #2:                  16mm Furring channel on direct fix clips
  • Acoustic insulation side #1:  Bradford 75mm ACOUSTIGARD 14kg/m3
  • Acoustic insulation side #2:   N/A

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.31 KOROK® KIR09 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                 177mm
  • Panel:                                   51mm
  • Density:                              600Kg/m³
  • STC:                                     60
  • FRR:                                     -/60/60
  • Cavity:                                 N/A
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Acoustic insulation side #1:  Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2:  Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.32 KOROK® KIR14 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                109mm
  • Panel:                                  51mm
  • Density:                             600Kg/m³
  • STC:                                     55
  • FRR:                                     -/60/60
  • Cavity:                                N/A
  • Lining side #1:                 1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                 N/A
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on resilient mounts
  • Frame side #2:                   N/A
  • Acoustic insulation side #1:  R1.3 GreenStuf® Masonry Wall Blanket 45mm
  • Acoustic insulation side #2:  N/A

Refer to KOROK® Intertenancy Apartments Systems for fixing details

 

KOROK® KIR Intertenancy Apartments with CeilingSystems (FRR -/120/120)

4.33 KOROK® KIR06 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                188mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    59
  • FRR:                                    -/120/120
  • Cavity:                                Min 20mm
  • Lining side #1:                 1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                 1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm steel frame
  • Frame side #2:                  N/A
  • Acoustic insulation side #1: ~
  • Acoustic insulation side #2:  N/A

Acoustic insulation side #1  GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.34 KOROK® KIR07 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                188mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    59
  • FRR:                                   -/120/120
  • Cavity:                               Min 20mm
  • Lining side #1:                 1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:                 1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm steel frame
  • Frame side #2:                  N/A
  • Acoustic insulation side #1: ~ 
  • Acoustic insulation side #2: N/A

Acoustic insulation side #1   GreenStuf® Sound Solution® Plus 75, or 75mm Pink Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.35 KOROK® KIR15 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                141mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    56
  • FRR:                                    -/120/120
  • Cavity:                                N/A
  • Lining side #1:                1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:      N/A
  • Head track protection: GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                 28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:               N/A
  • Acoustic insulation side #1: Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2:  N/A

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.36 KOROK® KIR16 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                 154mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                   57
  • FRR:                                  -/120/120
  • Cavity:                                N/A
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:               N/A
  • Acoustic insulation side#1: Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.37 KOROK® KIR17 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                204mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    61
  • FRR:                                    -/120/120
  • Cavity:                                N/A
  • Lining side #1:                1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                1x layer 13mm GIB Noiseline® plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Acoustic insulation side #1: Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2: Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.38 KOROK® KIR18 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                 204mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                   58
  • FRR:                                   -/120/120
  • Cavity:                                N/A
  • Lining side #1:                  1x layer 13mm GIB Noiseline® plasterboard
  • Lining side #2:                  1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Acoustic insulation side #1: Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2: Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.39 KOROK® KIR19 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                204mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    55
  • FRR:                                   -/120/120
  • Cavity:                                 N/A
  • Lining side #1:                 1x layer 13mm GIB® Standard plasterboard
  • Lining side #2:                 1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Frame side #2:                 28mm Furring channel on Rondo® BETAGRIP® Clips
  • Acoustic insulation side #1: Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2: Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.40 KOROK® KIR20 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                233mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    60
  • FRR:                                    -/120/120
  • Cavity:                               Min 15mm
  • Lining side #1:                   1x layer 13mm GIB Noiseline®
  • Lining side #2:                   1x layer 13mm GIB® Standard plasterboard
  • Head track protection:  GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                  64mm Steel frame
  • Frame side #2:                  28mm Furring channel on Rondo® BETAGRIP® Clips
  • Acoustic insulation side #1: Pink® Batts® R1.2 50mm 12.8 kg/m3
  • Acoustic insulation side #2: Pink® Batts® R1.2 50mm 12.8 kg/m3

Refer to KOROK® Intertenancy Apartments Systems for fixing details

4.41 KOROK® KIR21 INTER-TENANCY SYSTEM

  • Location:                            ~
  • Wall thickness:                262mm
  • Panel:                                 78mm
  • Density:                             400Kg/m³
  • STC:                                    69
  • FRR:                                    -/120/120
  • Cavity:                                Minimum 108mm between the framing – Note: Framing not to touch KOROK® panel.
  • Lining side #1:                1x layer 13mm GIB Noiseline®
  • Lining side #2:                1x layer 13mm GIB Noiseline®
  • Head track protection: GIB Fyreline® 13mm 120mm wide
  • Frame side #1:                 64mm Steel frame
  • Frame side #2:                 64mm Steel frame
  • Acoustic insulation side #1: Pink® Batts® R1.8 
  • Acoustic insulation side #2: Pink® Batts® R1.8

Refer to KOROK® Intertenancy Apartments Systems for fixing details

Read more
KOROK® Ceiling and Bulkhead Systems

Ceiling and Bulkhead Systems

Slide 1

KOROK® Ceiling and Bulkhead Systems

Simplifying Fire-Rated Ceiling & Bulkhead Design

A Smarter Approach to Fire-Rated Ceilings & Bulkheads

KOROK® Ceiling & Bulkhead Systems provide a smarter, more efficient approach to fire-rated ceiling construction for commercial, industrial, and infrastructure projects. Utilising KOROK® 78mm panels, these systems are designed to simplify fire continuity while enabling fast underside installation with Fire Resistance Ratings of up to -/120/120.

Developed to address the practical challenges faced on modern construction sites, KOROK® systems are ideal for service-heavy environments, restricted-access ceiling spaces, and complex construction sequencing. The lightweight panel design helps reduce installation complexity, minimise disruption to other trades, and improve overall site efficiency.

Traditional Fire-Rated Ceiling Construction Can Be Complex

Conventional fire-rated ceiling and bulkhead systems can create unnecessary challenges around ceiling plenums, service coordination, access limitations, and installation sequencing. In many cases, traditional systems require additional linings to be installed from above, increasing labour, programme time, and coordination requirements. KOROK® Ceiling & Bulkhead Systems simplify this process.

Designed specifically for installation from the underside, KOROK® systems reduce reliance on roof-space access while supporting efficient programme sequencing for new builds, retrofit projects, and staged construction works.

The symmetrical profile of the KOROK® 78mm panel allows seamless integration with KOROK® fire-rated wall systems, concrete/masonry, and structural steel elements. By utilising compatible KOROK® wall and ceiling systems together, fire continuity can be maintained without overcomplicating details or requiring excessive additional ceiling linings.

All KOROK® panel tasting has been carried out at nationally accredited laboratories to AS1530: Part 4, providing designers, engineers, and contractors with confidence in system performance and compliance. Keep it simple with lightweight, code-compliant KOROK® systems designed to work together to meet demanding fire and acoustic performance requirements.

Typical Applications Include:

  • Service corridors with ducts and services
  • Riser and duct bulkheads
  • Top of lift shafts
  • Fire egress
  • Corridors and lobbies
  • Inclined ceilings under escalators and stairs
  • High fire consequence rooms
  • Plant rooms

Key Advantages

  • Underside Installation Options
  • Fire Ratings of up to -/120/120
  • Fast & Efficient Installation
  • Simplified Fire Continuity
  • Lower-Mess Construction
  • Two-Way Fire Barrier Protection
  • Flexible Design Capability
  • Additional Lining Allowance
Read more

Floor Junctions

Slide 1

KOROK® Floor Junction Details for Comflor®, Double Tee, and CLT Floors.

Engineered Fire Integrity at the Wall‑to‑Floor Interface

Compliant Wall‑to‑Floor Solutions for Modern Construction

Created to support today’s complex building designs, KOROK® has developed a series of Floor Junction Details that strengthen, clarify, and enhance how KOROK® walls interface with modern floor construction, where fire performance matters most.

As building designs and structural systems evolve, KOROK® developed Floor Junction Details to strengthen existing requirements, increase technical clarity, and deliver more comprehensive CAD documentation – supporting accurate specification, smoother construction outcomes, and greater confidence from concept through consent and construction.

 

Why This Matters

In modern construction, fire performance is only as strong as the weakest interface. Unresolved wall-to-floor junctions can compromise fire separation, increase risk, and create uncertainty at design review or consent stage. KOROK® addresses this directly, ensuring continuity of fire cells where walls meet:

  • Profiled metal tray concrete floors 
  • Timber formwork and Stahlton rib systems
  • CLT and other structural floor types
  • Precast concrete floor (Double Tee)

These assessed solutions remove ambiguity and support compliant detailing across a wide range of building typologies.

Proven Fire Performance

KOROK® Floor Junction Details are supported by a formal engineering assessment, delivering verified fire performance aligned with regulatory expectations.

  • Up to -/120/120 FRR with KOROK® Panel 78mm
  • Up to -/60/60 FRR with KOROK® Panel 51mm
  • Valid for wall heights up to 6.0 metres
  • Based on testing to AS 1530.4 fire resistance standards

 

Engineered Flexibility for Real‑World Projects

Designed with practical construction and coordination in mind, KOROK® Floor Junction Details provide flexibility without sacrificing compliance. These engineered solutions accommodate:

  • Walls running parallel or perpendicular to floor profiles
  • Integration with deflection and non‑deflection head details
  • Compatibility with multiple structural systems without redesign

This allows engineers and architects the freedom to resolve complex interfaces while maintaining fire performance continuity.

See all KOROK® Floor Junction CAD details.

Comflor
Comflor detail example. View all Floor Junctions DWG files >>
Stahlton detail
Stahlton detail example. View all Floor Junctions DWG files >>
Double Tee detail
Double Tee detail example. View all Floor Junctions DWG files >>
CLT detail
CLT detail example. View all Floor Junctions DWG files >>

More Technical Resources

Read more
Butt Joints

Butt Joints

Butt Joints in Fire-Rated Walls: The KOROK Solution

When Fire Safety Meets Real-World Construction Challenges

Butt joints­­­­­ – where two panels meet end-to-end. KOROK® provides an engineered approach so your wall performs as designed across 51 mm (60-minute) and 78 mm (120-minute) KOROK internal panel systems.

Typical on-site scenarios: panels ordered too short, using leftover stock, restricted site access limiting panel length, or panel cuts needed for complex installations.

Applications

  • Single-panel butt joint
  • Double-panel butt joint

Methods (Butt Joints)

  • Profiled cover / steel flat plate – one or both sides, as detailed.
  • Back-to-back C-tracks – protected and unprotected variants.

Plugging Circular Holes (≤ Ø160 mm)

For small circular openings created during installation, repairs, or services, use KOROK-tested plug details to maintain system performance.

Methods

  • Fire-rated batt plug + steel flat plate
  • Fire-rated batt plug + fire-rated batt cover

Refer to the Detail Pack for FRR outcomes, fixing patterns, edge distances, sealant specification, and minimum spacings.

Read more

KOROK Access Panel Safe Removal & Reinstallation Procedure

KOROK Access Panel – Safe Removal & Reinstallation Procedure

 

⚠ WARNING – HEAVY PANEL

  • 480 mm x 480 mm (~27 kg)!
  • 600 mm x 480 mm (~33 kg)!
  • 900 mm x 480 mm (~50 kg)!

IN ACCORDANCE WITH NEW ZEALAND HEALTH & SAFETY REQUIREMENTS

  • Weight: This panel is heavy and may cause serious injury if not handled correctly.
  • Team Lift Mandatory: Always use at least two people or appropriate mechanical lifting equipment.
  • Wear Proper PPE: Use gloves, safety footwear, and any other required personal protective equipment.
  • Follow Lifting Procedures: Ensure you follow all site-specific and WorkSafe New Zealand guidelines, including a proper risk assessment before lifting.
  • Secure Installation: Confirm that the panel is securely supported during movement and installation.

Failure to use correct lifting methods and PPE may result in severe injury or property damage.

  • Applicable Panel Type: Fire-Rated Ceiling Access Panels
  • Panel Weight: Heavy (Team lift required)
  • PPE Required: Gloves, safety boots, hard hat, safety glasses

STEP 1. PREPARATION & SAFETY CHECKS

  1. Ensure all relevant site safety protocols and WorkSafe NZ guidelines are followed.
  2. Review the access panel warning label and lifting instructions prior to beginning.
  3. Conduct a job safety analysis (JSA) or task risk assessment.
  4. Inspect the work area for overhead hazards and confirm safe clearance for panel lowering.
  5. Confirm required PPE is worn and in good condition.
  6. Gather appropriate tools:
    • Socket set or spanners
    • Mechanical lifting aid (optional but recommended)
    • Clean drop cloth or secure storage pallet

STEP 2. SUPPORTING THE PANEL

  1. Before any bolts are loosened, ensure the panel is securely supported by:
    • Two competent personnel (manual lift), or
    • An approved mechanical lifting device.
  2. Support the panel from beneath to prevent any unplanned movement.

STEP 3. BOLT REMOVAL PROCEDURE

  1. Remove all perimeter bolts, retaining one bolt at each angle line to maintain panel stability.
  2. Do not remove any screws or TEK-type fasteners that:
    • Secure the panel frame to the hatch, or
    • Secure support angles to the ceiling C-track structure.

STEP 4. PANEL REMOVAL

  1. Once weight is fully supported and remaining bolts are accessible, remove the final two bolts.
  2. Carefully lower the panel straight down, ensuring no twist or torque is applied to the frame.
  3. Immediately place the panel on a prepared soft surface or pallet to avoid damage.
  4. Store panel in a secure, dry, and protected area free from impact risk.

STEP 5. CONDITION INSPECTION (PRE-REINSTALLATION)

Perform a full visual and physical inspection of the following components:

  1. Hatch door surface for warping, dents, or cracks
  2. Frame integrity including weld points and connection tabs
  3. Intumescent seal – check for continuous seal and any cracking or displacement
  4. Promatect® fire board – check for chipping, delamination, or moisture ingress

Replace any damaged or non-compliant components before proceeding with reinstallation.

STEP 6: REINSTALLATION PROCEDURE

  1. Position the access panel under the aperture using team lift or lifting device.
  2. Align the panel with the original bolt holes and insert bolts at each angleline.
  3. Once Securing nut and bolt assemblies are secured, reinstall remaining bolts in a crisscross pattern to ensure even loading.
  4. Torque all fasteners to manufacturer-recommended specification if available.
  5. Visually verify that the panel is flush with the ceiling and that all mechanical fixings are secured.

If you have any questions, please contact KOROK

info@korok.com or visit www.korok.com

Read more

Ceiling Access Panels

Slide 1

KOROK® Ceiling Access Panel

Fire-Rated Access Solutions for KOROK® Ceiling Systems

Designed For Access. Built For Protection

KOROK® 78mm Ceiling Access Panels provide compliant, high-performance fire-rated solutions for service access in fire-rated KOROK® Ceiling Systems. With versatile Fire Resistance ratings options, robust detailing, and ease of installation, they’re built to meet the demands of modern construction environments.

Engineered To Perform

KOROK® Ceiling Access Panels are compliant with the following FRRs:

Design Parameters

  • Maximum aperture size: 0.432 m²
  • Maximum length (parallel to panel): 900mm
  • Maximum width (perpendicular to panel): 750mm
  • Multiple apertures: minimum 500 mm clear distance between apertures (equivalent to two full KOROK® panels)
Standard Access Panel Size Available
480 x 480 600 x 480 900 x 480 Custom
Part Number PN1503 PN1501 PN1502
FRR -/60/60 • • • •
FRR -/120/120 • • • •

KOROK® Fire rated Ceiling Access Panels are designed to suit both the 60 minute and 120 minute fire resistance levels (FRL/FRR). within KOROK® Ceiling Systems.

System Components

A complete installation requires both the Access Panel and the matching Ceiling Aperture Pack.

1. Access Panel

This pack comprises:

  • 78mm KOROK® Ceiling Access Panel – Finish: Galvanised ZM275 (Coloursteel® on request)
  • Access Panel outer angle
  • KOROK® 5.5mm × 35mm screws
  • 20mm Promatect® 250 board Fire protection strips
  • 6g × 40mm self-drilling screws
  • KOROK® fire-rated sealant

2. Aperture Pack:

  • KOROK® C-track 60 × 80 × 60 × 1.55mm BMT
  • KOROK® fire-rated sealant
  • KOROK® Wafer Tek 10g × 16mm screws

Download Technical Data and CAD Drawing

Read more
Seismic Resource

Seismic Resource

Slide 1

KOROK® Seismic Resource

Setting the Benchmark for Seismic Resilience

Tested Beyond Code. Designed for Earthquake Performance.

KOROK® has set a new benchmark in seismic performance, demonstrating exceptional durability under rigorous in-plane and out-of-plane seismic testing. KOROK Panels have the ability to withstand high levels of drift , ensuring minimal damage, reduced repair costs, and faster recovery after earthquakes.

Leading the Market in Seismic Testing

KOROK® has recently undergone comprehensive seismic testing, setting a new benchmark to support our fire and acoustic wall performance. For over 25 years, we have delivered high-performance solutions across the residential, industrial, and commercial markets.

The Purpose Behind Our Testing

To understand and determine the behavior and performance of KOROK wall panels when subjected to seismic design loads occurring between structural slabs within buildings.

To demonstrate how KOROK® panels respond in correlation with drift levels for both in-plane and out-of-plane conditions, and to support the market with tested solutions. By undertaking this seismic testing, KOROK® reinforces its commitment to superior building resilience, helping to minimize damage, lower repair costs, and maintain operational continuity after earthquakes.

Importance of Seismic Resilience

The 2010/2011 Christchurch earthquakes and the more recent 2013 Lower North Island earthquakes illustrated the vulnerability of building non-structural elements (partitions, building services and piping). Widespread damage and loss of business continuity due to the poor performance of non-structural elements was widely observed

The Canterbury Earthquakes Royal Commission identified the need to improve the performance of non-structural elements in earthquakes with one of the recommendations focussed on improving non-structural element performance. “To prevent or limit the amount of secondary damage, engineers and architects should collaborate to minimise the potential distortion applied to non-structural elements. Particular attention must be paid to prevent the failure of non-structural elements blocking egress routes.”

Seismic Resource

Proven Seismic Performance

Conducted at BRANZ in 2024, our seismic tests followed FEMA 461 and NZS 1170.5:2004 standards, confirming KOROK® panels has the ability to withstand high levels of drift. No other system in New Zealand has undergone such rigorous testing with multiple wall configurations and variations.

Application in High-Importance Structures

As the ultimate All-in-One solution for fire & acoustic-rated wall systems, KOROK® panels offer unmatched performance for high-importance structures. With strong seismic performance and the ability to withstand high drift limits, KOROK® panels are ideal for IL3 and IL4 buildings, such as hospitals, emergency response centres, and essential utilities. KOROK® provides stakeholders, architects, and engineers with confidence in a durable, high-performance solutions.

Test Video of Typical Wall Configuration

In Plane 78mm KOROK® with head track fixing. Vertical panel installation with no apertures.

In-plane loading of 78mm KOROK® with head track fixing. Vertical panel installation with apertures.

Out of plane loading of 78mm KOROK® with head track fixing. Vertical panel installation with apertures.

Read more
Panel Handling

Panel Handling

Panel Handling

When discussing construction techniques, one important aspect to consider is panel handling, which ensures safety and efficiency on site.

KOROK manufactures lightweight wall panels consisting of galvanised or colour steel shells filled with aerated concrete.

Generally, KOROK products are delivered to your building or other site on long trailers and articulated trucks.

Our products are packed with reasonable protection against damage during delivery, however care must be exercised during unloading.

Forklift, Hiab or crane unload is required.

GUIDELINES

Ensure packs are lifted slowly, avoiding jerking where possible.

Panel Handling

Forklift unloading – 150mm between pack and mast.

Panel Handling

Ensure soft slings are neatly running on the inside of the two most inner timber collars of the pack.

Ensure soft slings are running continuously from the hooks to underneath the pack and back up to the hook.

Panel Handling

Do not loop the sling around itself with only one end connected to the hook. This may damage the panels when lifted.

Panel Handling

Ensure you lift only one or two packs at a time.

PACK SIZES

The panels are packed in timber pallets, measuring 1200mm wide by 300mm high.

There will be 2, 4 or 6 timber pallets for each pack (depending on length), nominally spaced 1200mm apart, middled from pack centre.

Packs can be stacked up to 6 packs high and must be placed side by side or end on end, on the truck / trailer tray.

When stacking back-to-back, timber collars must butt up against each other.

The length of the pack will vary according to the length of the panel required by the customer, commonly between 2.0 and 7.0 metres in length (can be up to 9.0m).

COMMON PACK WEIGHTS

Standard 3 metre pack = 390 – 470kg (nominal); Standard 6 metre pack = 780 – 936kg (nominal).

STRAPPING DOWN PACKS

Loads must be strapped down and secured by appropriate means. Load strops are most highly recommended, allowing 12 to 16 strops for a full semi load, more for B-Train transport.

Packs are to always be strapped over timber collars. No belly straps done with plastic angles at any time.

When stacking higher than 4 packs, a second set of straps must be placed after the third pack over timber collars only, before adding further packs.

ACCESSORIES

At times, a bundle of steel C-track or Angle strips may be placed on top of the load. These may measure up to 6.0 metres in length and weigh from 10kg to 500kg depending on the quantity.

IN TRANSIT

Where possible, avoid sudden braking and jolts during transit to reduce impacts on the product.

Re-tension strops every two hours at a minimum.

UNLOADING

Forklift, Hiab or crane unload is required.

Use soft slings or forks only, no chains to be used on product.

All lifting to only be done under middle crate, closest to the bearers to take the weight.

Forklift unloading – 150mm between pack and mast.

Care must be taken on unload and storage of product, avoiding bumps and scratching.

Guidelines must be carefully followed (turn over page).

Read more
Noise Control Systems

Noise Control Systems

KOROK Noise Control Systems – Additional Acoustic Solutions

Advanced Noise Control Solutions for Targeted Acoustic Performance

KOROK Building Systems introduces additional Acoustic solutions designed to tackle specific sound challenges in modern construction. Originally driven by the unique requirements of cinemas and terraced housing, these solutions bring versatile applications to a wide range of environments, enhancing comfort, privacy, and overall sound quality.

How Noise Control Systems Work

Our systems use a blend of wall densities and build-ups that are tailored to meet the specific acoustic needs of each project. By combining technical insights with flexible design, we provide solutions that integrate seamlessly into diverse building types while maintaining industry-leading standards in acoustic performance.

Key Applications of Noise Control Systems

  • Cinemas: Create immersive audio experiences without disruptive sound bleed between theaters, ensuring each audience enjoys undisturbed sound quality.
  • Terraced and Multi-Unit Housing: Reduce noise transfer between units to give residents a quieter, more comfortable living environment.
  • Other Specialized Spaces: Whether it’s office environments, hospitality spaces, or other commercial projects, our Noise Control Systems improve sound management, making shared and private spaces more acoustically efficient.

Why Choose KOROK Noise Control Systems?

Our additional acoustic solutions were developed with a focus on solving specialized acoustic issues. By studying the effects of various wall densities and configurations, we’ve created adaptable systems that address distinct sound transmission concerns. From minimizing sound bleed in high-traffic areas to achieving optimal acoustic separation between units, KOROK Noise Control Systems meet the needs of complex acoustic demands.

Read more
Deflection Head Details

Deflection Head Details

Slide 1

Deflection Head Details

Structural Flexibility Without Compromise

What Are Deflection Head Details?

Deflection head details are specialized components used in wall and partition systems to accommodate vertical or horizontal movement in a building’s structure. They are typically placed at the top of walls, allowing the structure to expand, contract, or shift without compromising the wall’s integrity or performance.

This movement can be caused by various factors, such as dead loads, live loads, thermal expansion, or seismic activity. At KOROK Building Systems, our deflection head solutions are designed to provide the flexibility and stability needed in high-performance wall systems.

KOROK deflection head details:

  • Maintain Structural Integrity: Designed to allow movement in walls without damaging the structure, these details help prevent cracking or separation in response to building movement.
  • Ensure Fire and Acoustic Performance: KOROK deflection heads are rigorously tested to retain fire resistance and acoustic ratings, even with movement, maintaining protection in all conditions.
  • Seismic Readiness: In New Zealand, where seismic activity can impact building structures, our deflection head designs are engineered to absorb and adjust to seismic forces, supporting safe and resilient structures.

Dead and live loads can cause significant deflection in some structures. KOROK® can provide deflection C-track details where deflection loadings are considered.

Whether used in commercial or residential projects, KOROK’s deflection head details meet the highest industry standards, offering a reliable solution for builders, architects, and contractors who prioritize safety, performance, and durability.

Read more